Cable terminationCable terminationCarefully remove the jacketing from the cable and expose one inch of the insulated wire conductors. Do not remove any insulation from the conductors. When the RJ-45 connector is crimped, the contacts inside will pierce the conductor insulation. Untwist the wires to within 1/8" of the jacket. Arrange the wires according to the cable spec (568B in this case). Flatten and align the wires. Make one straight cut across all the conductors, removing approximately 1/2" to ensure the ends are of equal length.
Slide the wires into a connector. The cable jacket should extend into the connector about 1/4" for strain relief. Orient the wires so connector Pin 1 aligns with cable Pin 1, etc. Hold the connector in front of you. With the locking tab down, Pin 1 is on the far left.
Insert the connector into a crimp tool. Make sure you’re using the proper die. Firmly squeeze the handles. They’ll lock in a ratcheting action. A final click indicates the connector is firmly latched.
Check your work using a continuity tester or cable certifier rated for the cable standard you’re installing. Your tester should be able to check for shorts, opens, or miswires.
|